Please use this identifier to cite or link to this item: http://eadnurt.diit.edu.ua/jspui/handle/123456789/14738
Title: Development of Mathematical Models of Energy Conversion Processes in an Induction Motor Supplied from an Autonomous Induction Generator with Parametric non-Symmetry
Authors: Chenchevoi, Volodymyr
Kuznetsov, Valeriy
Kuznetsov, Vitalii
Zachepa, Iurii
Chencheva, Olga
Chornyi, Oleksii
Kovzel, Maksim
Kovalenko, Viktor
Babyak, Mykola
Levchenko, Serhii
Keywords: induction generator
induction motor
mathematical model
hodograph
thermal model
regression analysis
КТТ (ЛФ)
Issue Date: 2021
Publisher: НВП ПП «Технологічний Центр», Харьків
Citation: Chenchevoi V., Kuznetsov V., Kuznetsov V., Zachepa Y., Chencheva O., Chornyi O., Kovzel M., Kovalenko V., Babyak M., Levchenko S. Development of Mathematical Models of Energy Conversion Processes in an Induction Motor Supplied from an Autonomous Induction Generator with Parametric non-Symmetry. Eastern-European Journal of Enterprise Technologies 2021. Vol. 4. № 8 (112). P. 67–82. DOI: 10.15587/1729-4061.2021.239146.
Abstract: ENG: The paper presents studies of the system “induction generator-induction motor” with parametric asymmetry on a mathematical model to determine the quality of generated electricity in load operating modes. A mathematical model of the “induction generator-induction motor” system has been developed taking into account losses in steel and parametric asymmetry. The analysis of the transient characteristics of an induction generator when a motor load is connected in symmetrical and asymmetrical modes of operation is carried out. The results of changes in the main characteristics of an induction motor at various degrees of parametric asymmetry in the generator are presented. The quality of the generated electricity was analyzed based on the calculations of the unbalance coefficients for each of the operating modes. The assessment of the thermal state in steady-state conditions was carried out using an equivalent thermal equivalent circuit. Thermal transients were investigated when starting an induction motor from an autonomous energy source based on an induction generator. On a thermal mathematical model, the study of the effect of the output voltage asymmetry on the heating of the connected induction motor was carried out. It is shown that the asymmetry of the output voltage of an induction generator reaches 3–10 % and causes overheating of the windings in excess of the permissible values. A regression model has been developed for studying the operating conditions of an induction motor when powered by an induction generator with an asymmetry of the stator windings. The use of the obtained equations will make it possible to determine the most rational combination of factors affecting the heating of the stator windings of induction machines, in which they will not overheat above the maximum permissible temperature values of the corresponding insulation classes.
Description: V. Kuznetsov: ORCID: 0000-0002-8169-4598, M. Babyak: ORCID: 0000-0001-5125-9133
URI: https://doi.org/10.15587/1729-4061.2021.239146
http://eadnurt.diit.edu.ua/jspui/handle/123456789/14738
ISSN: 1729-3774 (Print)
Other Identifiers: DOI: 10.15587/1729-4061.2021.239146